DP-5000 – Low cost differential pressure transmitter
The differential pressure transmitters of the DP-5000 series are used to measure differential pressure, overpressure and vacuum. They provide one pressure range and one output signal.
Version without display.


VISA/MASTERCARD, PAYPAL,
ANTICIPATED REMITTANCE OR DIRECT
PAYMENT WITH DELIVERY AT OUR
WHAREHOUSE.
CUSTOMER SERVICE: +39.02.6659.5982
| SKU | Model | Description | Price | Quantity | ||
|---|---|---|---|---|---|---|
| 47134 | DP-5000.6X3206 | Output: 4-20 mA 2-wire |
75 EUR | |||
| 47130 | DP-5000.623206 | Output: 4-20 mA 2-wire |
75 EUR | |||
| 47131 | DP-5000.633206 | Output: 4-20 mA 2-wire |
75 EUR | |||
| 47132 | DP-5000.643206 | Output: 4-20 mA 2-wire |
75 EUR | |||
| 47133 | DP-5000.653206 | Output: 4-20 mA 2-wire |
75 EUR | |||
| 47135 | DP-5000.663206 | Output: 4-20 mA 2-wire |
75 EUR | |||
| 46914 | DP-5000.673206 | Output: 4-20 mA 2-wire |
75 EUR | |||
| 46960 | DP-5000.683206 | Output: 4-20 mA 2-wire |
75 EUR |
Description
The differential pressure transmitters of the DP-5000 series are used to measure differential pressure, overpressure and vacuum. They provide one adjustable pressure range and one output signal.
Applications
Monitoring of gaseous, non-combustible and non-aggressive media.
Possible usage areas are:
- Building automation, air conditioning systems and clean room monitoring
- Valve and flap control
- Filter, ventilator and blower monitoring
- Control of air flows
Adjustable pressure range
The end of the pressure range can be reduced to 50% of its factory set full scale value simply by the use of a push-button.
Output signal
4 ... 20 mA. Other signals on request.
Easy offset calibration
The output signal can be calibrated to zero by pressing the push-button (pressure transmitter must be depressurised).
Configurable response time
The response time of the output signal can be configured using a jumper. If the jumper is in place the response time is slow (factory setting), which is useful for suppressing brief pressure peaks. If the application requires a fast response time the jumper must be removed.
Reset
The transmitter can be reset to its factory setting, just by pressing the push-button for >10 sec.
Measuring method
Piezoresistive pressure transducer.
Mounting position
Can be mounted in any position. The zero offset calibration eliminates any possible position error.
SPECIFICATIONS:
Output signal: 2-wire version
Medium: Air and non-combustible and non-aggressive gases
Working and storage temperature: -20 ... 70°C
Linearity (incl. hysteresis and repeatability): ≤ ±0.5% FS, min. ±1 Pa
Uncertainty (Total Error Band w/o long-term and temperature effects) : ±1% FS, min. ±1 Pa
Long-term stability: ≤ ±1% FS
Humidity: 0 ... 95 % rel, non-condensing
Electrical connection: Spring terminals for wires
Mounting: Screw mounting with serratedscrews
Housing material: ABS
Housing dimensions: approx. Ø 66 x 28 mm
Protection class according to:
EN 60529
CE Conformance