BZG - Zener barrier

Zener barriers are designed to limit energy which may appear in hazardous area.

Mounting: simple on DIN rail
Models: simple or double
Version: 1 channel on 13mm tightness
Installation in safe area or in Zone 2 in a IP54 housing (nA type of protection)
Front panel with removable label holder

Read more


VISA/MASTERCARD, PAYPAL,
ANTICIPATED REMITTANCE OR DIRECT
PAYMENT WITH DELIVERY AT OUR
WHAREHOUSE.



CUSTOMER SERVICE: +39.02.6659.5982

SKU Model Description Price Quantity
36636 BZG787+

Zener barrier for smoke detectors or clean contacts
1 CHANNEL
Input from EX zone: smoke detector or clean contacts
Floating ground connection
It does not require power supply
Screw terminals
Compact dimensions: 13x110 mm Depth 110 mm
3/4: U0 = 28V I0 = 89.31mA P0 = 625.2mW
2/3: Ua = 26.8V Ifm = 50mA RL = 341.3ohm

 

---------- ATEX / IECEx informations ----------
INERIS 11ATEX0024X / IECEx INE11.0009X
Group II (surface) - category (1) G/D
II(1) GD [Ex ia Ga] IIC, IIB or [Ex iaD Da] IIIC
II3(1) G Ex nA [ia Ga] IIC T4 Gc
Installation in safe zone or zone 2
For equipment installed in zone 0,1,2,20,21,22

120 EUR

Description

Mounting: simple on DIN rail
Models: simple or double
Version: 1 channel on 13mm tightness
Installation in safe area or in Zone 2 in a IP54 housing (nA type of protection)
Front panel with removable label holder


EC Type examination certificate number :
INERIS 11 ATEX 0024 X

IECEx conformity certificate :
INE 11.0009X

ATEX/IECEx classification :
II (1) GD [Ex ia Ga] IIC or [Ex ia Ga] IIB or [Ex iaD Da] IIIC
II 3 (1) G Ex nA [ia Ga] IIC T4 Gc
II 3 (1) G Ex nA [ia Ga] IIB T4 Gc

Documentation

Similar products

RDN - Intrinsically safe relay

Input: Switch or proximity sensor
Output: Switch (5A – 250V)
Supply: 24-48 VDC
Model: 2 channels and signal duplicator (1 input – 2 outputs)
Red LED for relay state, and green LED for presence of voltage
Installation : Safe area

BXNT - 4-20mA transmitter power supply

Input: 4/20mA 2 wires active or passive
Output: 4/20mA 2 wires active or passive
Supply: 24-48 VDC,
Model: 1 or 2 channels and signal duplicator (1 input – 2 outputs)
Setting: Adjustment potentiometer for the source and the curve on the front green LED for presence of voltage
Installation : Safe area

BZG - Zener barrier

Mounting: simple on DIN rail
Models: simple or double
Version: 1 channel on 13mm tightness
Installation in safe area or in Zone 2 in a IP54 housing (nA type of protection)
Front panel with removable label holder