BAPI - VOC Duct and Rough Service Sensor

● Available with a CO2 Equivalent Output (CO2e) or a Total VOC Output (TVOC)
● Ventilated BAPI-Box for Rough Service Areas and BAPI-Box with Aspiration Tube for Ducts
0 to 10 VDC Output

The
quality of the air that we breathe is essential to
our health and knowing the air quality level is the first step to improving it. BAPI’s VOC sensors provide that critical air quality information.

Read more


VISA/MASTERCARD, PAYPAL,
ANTICIPATED REMITTANCE OR DIRECT
PAYMENT WITH DELIVERY AT OUR
WHAREHOUSE.



CUSTOMER SERVICE: +39.02.6659.5982

SKU Model Description Price Quantity
42973 BA/VOC10-D-BB

Duct VOC Sensor
Output: 0-10 V
Range: 0-2000 ppm CO2 Equivalent Range
IP66 Enclosure

357 EUR
42974 BA/VOC10-V-BB

Harsh Environment VOC Sensor
Range: 0-2000 ppm CO2 Equivalent Range
Ventilated IP66 Enclosure

406 EUR

Description

The CO2 equivalent (CO2e) units combine the benefits of VOC sensors and the common application of CO2 sensors into one unit. It provides a VOC reading that correlates to a typical indoor CO2 level of 0 to 2,000 ppm. This allows the sensor’s output to be used for ASHRAE’s CO2-based VRP ventilation schedule.
The total VOC (TVOC) units provide a VOC reading that is the total concentration of all VOCs present in the space within a range of 0 to 2,500 ppb. This is often needed to meet 3rd party building certifications that require separate CO2 and VOC readings.
Additional information on VOCs and using the CO2e units in your ventilation strategy is available on our website and in the Air Quality section of our catalog.

The Duct unit uses an aspiration tube, while the Rough Service unit uses a ventilated BAPI-Box and is ideal for areas such as outdoor air plenums, equipment rooms, green houses and warehouses.


Power: (
Half-wave rectified)
12 to 24 VDC, 35 mA max
18 to 24 VAC, 4 VAmax
CO2e Unit Detection Range:
0 to 2,000 ppm CO2 equivalent
TVOC Unit Detection Range:
0 to 2,500 ppb
Sensing Element:
Micro-machined metal oxide
Start-Up Time:
15 minutes
Response Time:
<60 sec (after start-up time)
Selectable Output:
0 to 5 or 0 to 10 VDC > 10KΩ impedance
Wiring:
3 wires, 16 to 22 AWG
Cover LEDs for CO2e Models
(not available on TVOC Models):
Good, Green < 1,000 PPM
Fair, Yellow = 1,000 to 1,500 PPM
Poor, Red > 1,500 PPM
Operating Environment:
32 to 122°F (0 to 50°C)
5 to 95%RH non-condensing
Enclosure Material:
UV-Resistant Polycarbonate, UL94, V-0
Agency:
CE EN 61326-1:2013 EMC, UL, RoHS

Documentation

Similar products

BAPI - VOC Duct and Rough Service Sensor

● Available with a CO2 Equivalent Output (CO2e) or a Total VOC Output (TVOC)
● Ventilated BAPI-Box for Rough Service Areas and BAPI-Box with Aspiration Tube for Ducts
0 to 10 VDC Output

BAPI - CO2 Duct Sensor

• Automatic barometric pressure and temperature compensation
• Does not require annual calibration, and suitable for 24/7 application
• Traffic light status indication
• Set Up time less than 15 mins

BAPI-Stat “Quantum” CO2 Sensor

Automatic Barometric Pressure and Temperature Compensation
Optimized for Continuously Occupied Areas