950XP – I/P Transducer

495.00 

SPECIFICATIONS
Input: 4-20 ma
Output: see products
Air consumption: 3.0 scfh (0,11 m3/hr) at mid range
Supply pressure: 100 PSIG (7,0 bar) maximum
(Note supply pressure must be a minimum of 5 PSIG above maximum output)
Flow capacity: 4,5 SCFM (7,6 M3/HR) at 25 PSIG (1,7 bar) supply. 12 SCFM (20,0 m3/hr) at 100 PSIG (7,0 bar) supply.
Temperature limit: operating -40 to 160°F (-40 to 71°C). Storage -40 to 200°F (-40 to 93°C).
Loop load, I/P transducer: 7,5 Vdc@20mA.
Impedance: 260 Ohms @ 70°F.
Operating modes: direct, reverse or split range.

PERFORMANCE SPECIFICATIONS:
Accuracy, Hysteresis and repeatability:
 ±0,1% of span.
Deadband: 0,02% of span.
Position effect: Not noticeable effect.
Vibration effect: Less than ±1% of span under the following conditions: 5-15 Hz@0,8 in, constant displacement; 15-500 Hz @10 g’s.
Supply pressure effect: Not noticeable effect.
Temperature effect: ±0,045%°F (0,07% °C) of span.
Reverse polarity effect: No damage from reversal of normal supply current (4-20 mA) or from misapplication of up to 60 mA.

PHYSICAL SPECIFICATIONS:
Port size: 1/4″ NPT.
Media: clean dry, oil free, air filtered to 40 micron.
Materials: Housing Chromate-treated aluminium with epoxy baked paint NEMA 4X (IP 65).
Elastomers: Buna-N.
Trim: stainless steel; Brass; Zinc plated steel.
Weight: 1,8 lbs (0,82 kg).

HAZARDOUS AREA CLASSIFICATION
Factory Mutual (FM) & Canadian Standards Approval (CSA)

Explosion Proof
Class I, Division 1 & 2, Groups B, C & D
Enclosure Nema 4X (IP 65)
Temp. Code T6 Ta = 70° C

Dust Ignition Proof
Class II & III, Division 1, Groups E, F & G
Enclosure Nema 4X(IP 65)
Temp. Code T6 Ta = 70° C

Intrinsically Safe
Class I, Division 1, Groups C & D
Class II, Division 1, Groups E, F, & G
Class III, Division 1, Fibers
Enclosure Nema 4X(IP 65)
Rated 4-20 mA, 30 VDC Max.
Temp. Code T4 Ta = 70° C

Non-Incendive
Class I, Division 2, Groups A, B, C & D
Enclosure Nema 4X(IP 65)
Temp. Code T4 Ta = 70° C

Suitable for
Class II & III, Division 2, Groups F & G
Enclosure Nema 4X(IP 65)
Temp. Code T6 Ta = 70° C

Entity Parameters
U: (Vmax) = 30 VDC Ci = 0 uF
I: (Imax) = 125 mA Li = 0 m H
Pi = .7 w

ATEX Approval
FM06ATEX0018X II 2 G Ex d IIB + H2 T6 Ta = -20°C to +70°C
FM06ATEX0027X II 1 G Ex ia IIB T4 Ta = -40°C to +70°C
FM06ATEX0028X II 3 G Ex nA nL IIC T6 Ta = -40°C to +70°C

Entity Parameters
Ui (Vmax) = 30 VDC Ci = 0 uF
Ii (Imax) = 125 mA Li = 0 mH
Pi = .7 W Max.

SKU: N/A Category: Tags: ,

Product available - for orders before 12.00, shipping the same day.
(In case of payment by bank transfer, shipment will be made upon payment received).

Product temporarily out of stock - average delivery time: 10-20 days.

950XP - I/P Transducer - 950-ACK 950-ACK Code: 7112

Input: 4-20 mA
Output: 3 -15 PSI ( 0,2 – 1,0 Bar)
ATEX certified

495.00 
-
+
950XP - I/P Transducer - 950-ADK 950-ADK Code: 8174

Input: 4-20 mA
Output: 3 -27 PSI ( 0,2 – 1,9 Bar)
ATEX certified

495.00 
-
+
950XP - I/P Transducer - 950-AEK 950-AEKCode: 9481

Input: 4-20 mA
Output: 6 – 30 PSI ( 0,4 – 2.0 Bar)
ATEX certified

495.00 
-
+