TFLOW T122 – Air velocity sensor Ø 22mm

148.00 172.00 

T122 is an Aluminium air velocity sensor with measuring head material in Macromelt®. Able to measure air flow velocity on diffusers outputs, HVAC systems, used on fan monitoring, flow hood or filters monitoring and simple velocity monitoring on ventilation systems.

Fluids: air and compatible gases not combustible
Accuracy : ±2.5% f.s. ±0.1 m/s @ 25°C
±3.5% f.s. ±0.1 m/s @ 25°C ( for range 0-1 m/sec)
Response time: 1 second  up to 95% of final value
Temperature limits : process  from  5 to 50°C, ambient  from   0 to 50°
Pressure limits: 0.5 Bar
Humidity  limits: 5-95% ur not condensing
Power supply: 18-26 VDC
Available ranges: 0-3, 0-10, 0-20, 0-30 m/sec
Outputs:  0-10 V,  4-20 mA (3 wires),
Loop resistance: 500 ohm max
Current consumption : 100 mA max
Electrical connection: :  M12 connector (see accessories to purchase suitable cable ) or terminal block
Mounting orientation : probe to be mounted aligned to flow direction
Materials:  sensor: glass ceramic; measuring head: macromelt®; probe: anodized aluminium.
Certificate: CE

SKU: N/A Category:
Download:

Product available - for orders before 12.00, shipping the same day.
(In case of payment by bank transfer, shipment will be made upon payment received).

Product temporarily out of stock - average delivery time: 10-20 days.

TFLOW T122 – Air velocity sensor Ø 22mm - T122/A/M12/4/1 T122/A/M12/4/1 Code: 33819

Range : 0 – 1 m/s
Output : 4-20 mA (3 wires)
Electrical connection: M12
Material: Anodized aluminium and Macromelt® head
Probe length: 218 mm

148.00 
-
+
TFLOW T122 – Air velocity sensor Ø 22mm - T122/A/M12/4/3 T122/A/M12/4/3 Code: 29097

Range : 0 – 3 m/s
Output : 4-20 mA (3 wires)
Electrical connection: M12
Material: Anodized aluminium and Macromelt® head
Probe length: 218 mm

148.00 
-
+
TFLOW T122 – Air velocity sensor Ø 22mm - T122/A/M12/4/10 T122/A/M12/4/10 Code: 32522

Range : 0 – 10 m/s
Output : 4-20 mA (3 wires)
Electrical connection: M12
Material: Anodized aluminium and Macromelt® head
Probe length: 218 mm

148.00 
-
+
TFLOW T122 – Air velocity sensor Ø 22mm - T122/A/M12/4/20 T122/A/M12/4/20 Code: 28645

Range : 0 – 20 m/s
Output : 4-20 mA (3 wires)
Electrical connection: M12
Material: Anodized aluminium and Macromelt® head
Probe length: 218 mm

148.00 
-
+
TFLOW T122 – Air velocity sensor Ø 22mm - T122/A/M12/4/30 T122/A/M12/4/30 Code: 29096

Range : 0 – 30 m/s
Output : 4-20 mA (3 wires)
Electrical connection: M12
Material: Anodized aluminium and Macromelt® head
Probe length: 218 mm

148.00 
-
+
TFLOW T122 – Air velocity sensor Ø 22mm - T122/A/MRS/4/1 T122/A/MRS/4/1 Code: 33817

Range : 0 – 1 m/s
Output : 4-20 mA (3 wires)
Electrical connection: terminal block
Material: Anodized aluminium and Macromelt® head
Probe length: 300 mm

172.00 
-
+
TFLOW T122 – Air velocity sensor Ø 22mm - T122/A/MRS/4/3 T122/A/MRS/4/3 Code: 33813

Range : 0 – 3 m/s
Output : 4-20 mA (3 wires)
Electrical connection: terminal block
Material: Anodized aluminium and Macromelt® head
Probe length: 300 mm

172.00 
-
+
TFLOW T122 – Air velocity sensor Ø 22mm - T122/A/MRS/4/10 T122/A/MRS/4/10 Code: 33814

Range : 0 – 10 m/s
Output : 4-20 mA (3 wires)
Electrical connection: terminal block
Material: Anodized aluminium and Macromelt® head
Probe length: 300 mm

172.00 
-
+
TFLOW T122 – Air velocity sensor Ø 22mm - T122/A/MRS/4/20 T122/A/MRS/4/20 Code: 33815

Range : 0 – 20 m/s
Output : 4-20 mA (3 wires)
Electrical connection: terminal block
Material: Anodized aluminium and Macromelt® head
Probe length: 300 mm

172.00 
-
+
TFLOW T122 – Air velocity sensor Ø 22mm - T122/A/MRS/4/30 T122/A/MRS/4/30Code: 33816

Range : 0 – 30 m/s
Output : 4-20 mA (3 wires)
Electrical connection: terminal block
Material: Anodized aluminium and Macromelt® head
Probe length: 300 mm

172.00 
-
+

Accessories